Skip to content

Engineering Guide

HVAC Engineer's Unit Conversion Cheat Sheet: BTU, kW, Ton, CFM, ACH

Published June 12, 2026 · by Industrial Unit Converter Editorial Team

Why HVAC conversion fluency matters

HVAC design pulls from three different unit systems daily: US imperial (BTU, tons, CFM, FPM), SI metric (kW, m³/h, m/s), and hybrid conventions (ACH, wet bulb, EER, COP). Mixing up these systems during equipment selection, energy modeling, or commissioning is one of the most common — and costly — engineering errors.

Consider a chiller bid: a US manufacturer quotes 50 tons, a European competitor quotes 176 kW. Are they the same equipment? Yes — but only if you know 1 ton = 3.517 kW. A designer who can't make this conversion instantly might spec mismatched cooling towers, pumps, and electrical services.

This cheat sheet covers the everyday conversions organized by the task at hand, with worked examples and the underlying physics where it matters.


Thermal power: BTU/hr ↔ kW ↔ Refrigeration Tons

These three units define every heating and cooling capacity specification. You'll use at least one of these conversions on every project.

From To Multiply by Quick mental shortcut
BTU/hr kW 0.000293 Divide by 3,412
kW BTU/hr 3,412 A 10 kW heater = 34,120 BTU/hr
Tons (RT) kW 3.517 1 ton = 12,000 BTU/hr = 3.517 kW
kW Tons 0.2843 Divide by 3.517
BTU/hr Watts 0.2931 A 1,000 BTU/hr baseboard = 293 W
EER kW/ton 12 ÷ EER An EER 12 unit = 1.0 kW/ton

Common equipment sizes to memorize:

Capacity BTU/hr Tons kW
Residential window AC 12,000 1 3.52
Small commercial rooftop 60,000 5 17.6
Medium commercial 120,000 10 35.2
Large commercial boiler 500,000 41.7 146.6
Industrial chiller 3,000,000 250 879

Worked example: comparing US and European chiller bids

You receive two proposals for a new chiller plant:

  • Bid A (US): 150 tons at 0.62 kW/ton
  • Bid B (EU): 528 kW at EER 19.4

Are they equivalent?

Bid A: 150 tons × 3.517 = 527.6 kW, and 150 × 0.62 = 93.0 kW input Bid B: 528 kW capacity, and 528 ÷ 19.4 = 27.2 kW input

Both provide ~528 kW of cooling, but Bid B uses only 29% of the input power — a dramatically more efficient machine. Without the tons-to-kW conversion, you might have overlooked this entirely.

Use our BTU/hr to kW Calculator for any combination of these units, and Refrigeration Tons to kW for chiller comparisons.


Airflow: CFM ↔ m³/h ↔ ACH ↔ Velocity

Airflow conversions connect duct sizing, ventilation code compliance, and equipment specifications across US and metric systems.

From To Multiply by Typical context
CFM m³/h 1.699 European AHU catalog comparison
m³/h CFM 0.5886 US equipment from metric specs
CFM L/s 0.4719 Laboratory fume hoods
CFM L/min 28.32 Medical gas, process air
ACH CFM (ACH × Room ft³) ÷ 60 Ventilation design
CFM ACH (CFM × 60) ÷ Room ft³ Code compliance check

Typical ACH guidelines by space type (commonly referenced in industry practice, derived from ASHRAE 62.1 ventilation rates and other standards):

Space Type Recommended ACH Notes
Offices 4-6 Based on occupant density
Classrooms 5-7 Higher for younger children
Laboratories 6-12 Depends on fume hood count
Hospital OR 15-20 Positive pressure, HEPA filtered
Cleanroom ISO 7 60+ Entire volume exchanged per minute

Worked example: sizing ventilation for a classroom

A 900 ft² classroom with 9 ft ceilings (8,100 ft³) requires 6 ACH per ASHRAE 62.1.

Required CFM = (ACH × ft³) ÷ 60 = (6 × 8,100) ÷ 60 = 810 CFM

If the spec called for 15 CFM per person for a classroom of 25 students, that would be 375 CFM — less than half of what the ACH method requires. Always calculate both methods and use the larger value.

Use our ACH to CFM Calculator and Air Changes Per Hour Calculator for direct room-by-room calculations. For duct velocity conversions, see our m/s to FPM Converter.


Sensible and latent heat: the split every load calculation needs

Cooling load is always the sum of two components. Treating them as one number is the most common cause of uncomfortable, clammy spaces.

Total Cooling = Sensible Heat + Latent Heat

Component Formula What it handles Typical share
Sensible (Qs) 1.08 × CFM × ΔT (BTU/hr) Temperature change (dry bulb) 70% in dry climates
Latent (Ql) 0.68 × CFM × ΔW (BTU/hr) Moisture removal (condensation) 30% in humid climates
Total (Qt) 4.5 × CFM × Δh (BTU/hr) Combined sensible + latent 100%
Sensible (SI) 1.23 × L/s × ΔT (Watts) Temperature change (metric)
Latent (SI) 3.0 × L/s × ΔW (Watts) Moisture removal (metric)

Where: ΔT = dry bulb temperature difference (°F or °C), ΔW = humidity ratio difference (grains/lb or g/kg), Δh = enthalpy difference (BTU/lb or kJ/kg).

Worked example: classroom in Miami vs Denver

A 900 ft² classroom needs 810 CFM (from the example above). Design supply air is 55°F, return air is 75°F (ΔT = 20°F).

Sensible load: Qs = 1.08 × 810 × 20 = 17,496 BTU/hr

Now for latent load. In Miami (85 gr/lb outdoor, 65 gr/lb return, ΔW = 20): Ql = 0.68 × 810 × 20 = 11,016 BTU/hr Total = 17,496 + 11,016 = 28,512 BTU/hr (39% latent)

In Denver (30 gr/lb outdoor, 65 gr/lb return, ΔW = -35 — actually adding moisture): Ql = 0.68 × 810 × (-35) = -19,278 BTU/hr (humidification needed) Total = 17,496 + (-19,278) = net different profile entirely

The same classroom in two climates has fundamentally different equipment requirements. A Miami engineer who ignores latent load spec's a coil that hits temperature but leaves the space at 70% RH.

Use our Sensible Heat Calculator and Latent Heat Calculator for automated psychrometric splits.


CFM per ton: the most abused rule of thumb in HVAC

The "400 CFM per ton" rule is useful as a starting point — but dangerous when applied blindly.

Application Typical CFM/ton Why
Comfort cooling (standard) 350-400 55°F supply air, 75°F return, ΔT ≈ 20°F
High latent load (humid) 300-350 Deeper coil for more dehumidification
Dry climate (sensible only) 400-450 Less moisture to remove
Data center / process 200-300 High ΔT design, sensible-only load
Hospital OR 15-20 ACH drives Ventilation-driven, not load-driven
100% outdoor air (DOAS) Varies widely Depends on outdoor conditions and energy recovery

The physics behind the rule:

CFM/ton derives from Q = 1.08 × CFM × ΔT, where Q = 12,000 BTU/hr per ton:

CFM/ton = 12,000 ÷ (1.08 × ΔT)

At ΔT = 20°F: CFM/ton = 12,000 ÷ (1.08 × 20) = 556 (not 400!)

The 400 CFM/ton number actually assumes a ΔT closer to 28°F, or it bundles in some latent capacity. At 16°F ΔT (chilled beam or radiant system), it becomes 694 CFM/ton. The rule only works when your system design matches the assumption behind it.

Use our CFM per Ton Calculator for load-specific numbers. For complete load calculation methodology, see our HVAC Load Calculation Guide.


Wet bulb, dry bulb, and psychrometric conversions

Psychrometric calculations often require wet bulb temperature as input, but field instruments frequently measure relative humidity instead.

When the conversion matters:

  • Cooling tower selection: Tower approach is based on the difference between leaving water temperature and ambient wet bulb, not dry bulb or RH
  • Evaporative cooling design: Wet bulb depression (dry bulb minus wet bulb) determines the maximum achievable temperature drop
  • ASHRAE 55 comfort compliance: Uses operative temperature and humidity ratio, both derived from psychrometric state points
  • Energy recovery: Enthalpy wheels and ERV effectiveness curves reference wet bulb conditions
Condition Dry Bulb Wet Bulb RH Dew Point
Phoenix summer 110°F 65°F 5% 35°F
Miami summer 92°F 80°F 60% 76°F
Office (design) 75°F 62.5°F 50% 55°F
Data center (supply) 72°F 58°F 45% 50°F

Use our Wet Bulb to Relative Humidity Calculator for quick conversions without a psychrometric chart.


Pressure and duct static conversions

From To Multiply by Use case
in H₂O psi 0.0361 Duct static to pressure
in Hg psi 0.4912 Vacuum and refrigerant
Pa in H₂O 0.00402 European fan curves to US
psi in H₂O 27.68 Refrigerant pressure to airflow equivalent
kPa in H₂O 4.02 SI fan curves to US duct design

Fan power is proportional to CFM × static pressure. Overestimating duct static by just 0.5 in H₂O over-specs the fan motor by 20% — a common cause of oversized VFDs and unnecessary energy consumption.

For cleanroom and laboratory pressurization calculations, see our Static Pressure to CFM Calculator. For the full treatment of pressure units across all engineering domains, read our Pressure Units: A Practitioner's Guide.


Frequently asked questions

Q: Why is a refrigeration ton 12,000 BTU/hr?

One ton of refrigeration is the cooling rate required to freeze one short ton (2,000 lb) of water at 32°F into ice at 32°F in 24 hours. The latent heat of fusion for water is 144 BTU/lb, so: 2,000 lb × 144 BTU/lb ÷ 24 hours = 12,000 BTU/hr. This dates from the ice-house era when cooling was measured in tons of ice consumed per day.

Q: When should I use EER vs COP vs kW/ton?

EER (BTU/hr per watt) and COP (kW out per kW in) measure the same thing in different units: COP = EER ÷ 3.412. kW/ton is the inverse — lower is better. Use EER for unitary equipment (rooftops, splits), COP for chillers and heat pumps (especially in SI markets), and kW/ton for chiller plant efficiency comparisons.

Q: How do I convert CFM to kg/s for mass flow calculations?

First convert CFM to m³/s (CFM × 0.0004719), then multiply by air density (typically 1.2 kg/m³ at 20°C sea level). For precise work, correct the density for actual temperature and altitude — our CFM to m³/h Converter and SCFM to ACFM Calculator handle the density corrections.

Q: Can I use the 400 CFM/ton rule for a VRF system?

No. VRF systems typically operate at higher ΔT and variable airflow. A VRF indoor unit at part load might deliver 250-300 CFM/ton while still meeting the load. Always use manufacturer selection software for VRF — the rules of thumb for constant-volume systems don't apply.

Q: What's the difference between ACH and CFM/ft²?

ACH is volumetric — it exchanges a fixed percentage of room volume per hour regardless of ceiling height. CFM/ft² is area-based — it supplies the same airflow regardless of ceiling height. A warehouse with 30 ft ceilings needs dramatically different CFM under each method. Always cross-check both.


The 5 conversions every HVAC engineer should memorize

  1. BTU/hr → kW: ÷ 3,412 (or × 0.000293)
  2. Tons → kW: × 3.517 (1 ton = 12,000 BTU/hr)
  3. CFM → m³/h: × 1.699
  4. ACH → CFM: (ACH × ft³) ÷ 60
  5. m/s → FPM: × 196.85

Related tools and further reading

Calculators:

Related articles:

← All HVAC Converters