PSIA to PSIG Converter
PSIA (pounds per square inch absolute) is the pressure referenced to a perfect vacuum (0 PSIA = no molecular motion). PSIG (pounds per square inch gauge) is the pressure referenced...
Formula
Source: Engineering Toolbox | Last reviewed: June 8, 2026
Examples
14.696 psia
= 0 psig
- P_atm_psi = 14.696
Atmospheric pressure = 0 psig at sea level
114.696 psia
= 100 psig
- P_atm_psi = 14.696
100 psig vessel = 114.7 psia
12 psia
= -2.7 psig
- P_atm_psi = 14.696
Below atmospheric = vacuum (negative psig)
Quick Reference Table
| PSIA | PSIG |
|---|---|
| 14.7 | 0 |
| 24.7 | 10 |
| 64.7 | 50 |
| 114.7 | 100 |
| 214.7 | 200 |
| 514.7 | 500 |
Where is this used?
Compressor discharge pressure conversion from thermodynamic calculations (absolute) to operating setpoints (gauge).
Safety valve settings verification.
In the design of pressure vessels and boilers per ASME BPVC Section I (Power Boilers) and Section VIII (Pressure Vessels), the maximum allowable working pressure (MAWP) is stamped on the nameplate in PSIG (or kPa, bar) for the US market, but the stress calculations in the design report are done with absolute pressure because the design fatigue cycle is referenced to the absolute lower bound.
A boiler designed for 1,000 PSIG operating pressure (1,014.7 PSIA) and a 20,000-cycle fatigue life requires the stress range calculation to use the full absolute pressure range, with the conversion applied at the stress calculation step.
In the design of steam turbines, gas turbines, and large centrifugal compressors, the performance map uses pressure ratio (a dimensionless quantity) plotted against corrected speed and flow, with the inlet pressure explicitly in PSIA.
The discharge pressure gauge reading (PSIG) is then derived from the PSIA discharge and the local atmospheric pressure.
Safety relief valve sizing per API 520 and API 521 is done using the set pressure in PSIG (or kPa, bar) at the valve inlet, but the superimposed back pressure and the atmospheric pressure must be accounted for in the calculation using absolute pressures, with the conversion applied to the set pressure plus the atmospheric pressure to get the absolute pressure at the valve inlet.
The set pressure of a 100 PSIG safety valve on a vessel at 5,000 ft elevation with P_atm = 12.23 PSIA means the valve opens at 112.23 PSIA, a value that must be used in the mass flow calculation for the required orifice area.
In the SCADA and DCS systems of refineries, chemical plants, and power plants, pressure transmitters typically measure PSIG (or the differential pressure) and the control system displays the value in the operator's preferred unit — the underlying HART, Foundation Fieldbus, or PROFIBUS configuration must be aware of the atmospheric pressure reference, especially at elevated plant sites or at plants with barometric pressure variations, and the calibration certificate of the transmitter must specify the reference conditions.
Frequently Asked Questions
Why does a gauge read zero at atmospheric pressure?
Most pressure gauges measure the difference between the process pressure and ambient air pressure. Since both sides of the sensing element see the same atmospheric pressure, the gauge reads zero. Only sealed absolute pressure gauges can read atmospheric pressure directly.
How does this differ from PSIG to PSIA conversion?
They are inverse operations. PSIG to PSIA adds atmospheric pressure; PSIA to PSIG subtracts it. Use PSIA to PSIG when you have absolute pressure from a calculation and need the gauge equivalent for operations.
Can psig be negative?
Yes. Any psia value below local atmospheric pressure produces a negative psig value, indicating vacuum. For example, 10 psia at sea level = −4.696 psig. This is perfectly valid and common in suction-side piping.
Reviewed for accuracy
· Last reviewed: June 8, 2026
All calculations are for reference only. Always verify with manufacturer data and a qualified engineer for critical applications. Learn about our editorial process.