Skip to content

Voltage Drop Calculator (AC)

Voltage drop is the reduction in voltage along a conductor as current flows through it, dictated by Ohm's Law (V = I × R) and fundamentally unavoidable in any real circuit. The...

Advanced options

Quick try

Formula

Source: IEEE 141 (Red Book), NEC Chapter 9 Table 8, NFPA 70 | Last reviewed: July 26, 2026

Examples

200 Amps

= 13.3 Volts

  • length = 500
  • voltage = 480
  • material = 1
  • awg_size = 0.1678
  • phase_factor = 1.732

200 A at 480V 3-phase #3/0 Cu 500 ft = 13.3 V (2.8% VD)

20 Amps

= 5.9 Volts

  • length = 150
  • voltage = 120
  • material = 1
  • awg_size = 12
  • phase_factor = 1

20 A at 120V single-phase #12 Cu 150 ft = 5.9 V (4.9% — exceeds NEC 3%)

400 Amps

= 6.7 Volts

  • length = 300
  • voltage = 208
  • material = 1
  • awg_size = 0.4
  • phase_factor = 1.732

400 A at 208V 3-phase 400 kcmil Cu 300 ft = 6.7 V (3.2%)

Quick Reference Table

Common Copper Wire Sizes — Circular Mils (CM) Table
AWG / kcmilCircular MilsAmpacity (75°C Cu)Resistance (Ω/1000 ft)
#14 AWG4110203.14
#12 AWG6530251.98
#10 AWG10380351.24
#8 AWG16510500.778
#6 AWG26240650.491
#4 AWG41740850.308
#2 AWG663601150.194
#1/0 AWG1056001500.122
#2/0 AWG1331001750.0967
#3/0 AWG1678002000.0766
#4/0 AWG2116002300.0608
250 kcmil2500002550.0515
500 kcmil5000003800.0258
750 kcmil7500004750.0172
NEC Recommended Voltage Drop Limits
Circuit TypeNEC ReferenceMax VD (%)Enforceable?
Branch Circuit210.19(A) Info. Note 43%No (informational)
Feeder215.2(A) Info. Note 22%No (informational)
Feeder + Branch Combined210.19(A) Info. Note 45%No (informational)
Fire Pump (running)695.75%Yes (mandatory)
Fire Pump (starting)695.715%Yes (mandatory)
Sensitive EquipmentIEEE 1411-2%Design practice
ASHRAE 90.1 Energy Code90.1-2019 §8.42% feedersYes (energy code)

Popular Conversions

Quick answers for the most-searched Amps to Volts values.

Voltage drop 200 amp 480V 500 feet

200 Amps = 13.3 Volts

200 A 480V 3-phase on #3/0 Cu (167,800 CM) over 500 ft = 13.3V (2.8% drop). Acceptable per NEC 5% guideline. For 1,000 ft, upsize to 500 kcmil Cu.

Voltage drop 20 amp 120V 150 feet

20 Amps = 5.9 Volts

20 A 120V single-phase on #12 Cu 150 ft = 5.9V (4.9% drop). Exceeds NEC 3% branch circuit recommendation. Upsize to #10 AWG (3.7V, 3.1%) or #8 AWG (2.3V, 1.9%).

Voltage drop 400 amp 208V 300 feet

400 Amps = 6.7 Volts

400 A 208V 3-phase on 400 kcmil Cu 300 ft = 6.7V (3.2%). Near the 3% limit. For continuous loads requiring <3%, upsize to 500 kcmil (5.4V, 2.6%).

12V voltage drop 50 amp 15 feet

50 Amps = 0.74 Volts

50 A 12V DC on #6 Cu 15 ft = 0.74V (6.2% drop). Exceeds 3% DC guideline. For inverter circuits, use #4 AWG (0.47V, 3.9%) or keep cable run under 8 ft.

Voltage drop fire alarm NAC circuit

2 Amps = 0.4 Volts

2 A 24V DC on #14 Cu 200 ft = 0.79V (3.3%). Fire alarm NAC circuits per NFPA 72 have stricter requirements. Use #12 AWG (0.50V, 2.1%) to maintain signal integrity at end-of-line devices.

Where is this used?

Voltage drop calculation underpins virtually every electrical design decision beyond simple ampacity selection.

(1) Branch circuit final verification — after selecting a conductor for ampacity per NEC 310.16, the designer runs the voltage drop calculation.

If the 3% (branch) or 5% (feeder+branch) recommendation is exceeded, the next larger conductor size is selected.

A common scenario: a 30 A, 208V single-phase rooftop HVAC circuit at 250 ft with #10 AWG copper (10,380 CM) would show VD = (2 × 250 × 12.9 × 30) ÷ 10,380 = 18.64 V = 8.96% — clearly unacceptable, requiring at minimum #6 AWG (26,240 CM → 3.54% VD, still marginal) or #4 AWG (41,740 CM → 2.23% VD).

(2) Motor starting voltage dip verification — during across-the-line starting, motor inrush current reaches 6-8 times full-load current.

A 100 HP, 460V motor with FLA = 124 A and LRA = 6 × 124 = 744 A must maintain at least 85% of rated voltage at terminals during start.

The design VD check runs twice: once at FLA for steady-state compliance, and once at LRA to verify the starter contactor won't drop out and the motor will develop sufficient breakaway torque.

This often forces one to two AWG sizes larger than ampacity alone suggests.

(3) Fire pump circuits — NEC 695.7 mandates a maximum 15% voltage drop at the fire pump controller line terminals during motor locked-rotor starting.

This is one of the few enforceable (not just recommended) voltage drop requirements in the NEC, reflecting life-safety criticality.

A 200 HP fire pump at 460V (FLA ≈ 240 A, LRA ≈ 1,450 A) over a 150 ft service entrance requires 500 kcmil copper to stay within 15% VD at locked rotor.

(4) Renewable energy interconnection — utility-scale solar PV inverters feed power through medium-voltage step-up transformers to the point of interconnection.

Voltage rise (reverse voltage drop) from inverter to PCC must stay within ANSI C84.1 Range A limits (±5% of nominal).

This requires calculating VD with power flow reversed — the inverter is the source, the grid is the load — and ensuring the resulting voltage rise doesn't cause the inverter to trip on overvoltage during peak production.

(5) Data center power distribution — server power supplies are typically specified for 100-240V ±10% input.

A 415/240V three-phase PDU feeding rack PDUs via 50 ft whips must keep end-of-cable voltage above 216V under full load (30 A per phase).

This VD calculation governs the PDU whip gauge selection and often forces 10 AWG for 30 A circuits where ampacity would allow 12 AWG.

(6) Temporary construction power — portable spider boxes and long extension cords create severe voltage drop hazards.

OSHA requires that tools operate within manufacturer voltage tolerances.

A 100 ft, #12 AWG extension cord carrying a 15 A saw at 120V drops 5.9V (4.9%) — exceeding the 3% design target but typically within the saw's operating tolerance.

However, two 100 ft cords daisy-chained drop 11.8V (9.8%), which can cause universal motors to stall under load and overheat.

(7) Airport airfield lighting — series circuits operating at 6.6 A constant current over miles of #8 AWG cable use voltage drop to determine the maximum number of fixtures per series loop and the required regulator output voltage (often 5-20 kV).

(8) Subsea and downhole applications — long cable runs (thousands of feet) for submersible pumps and remote-operated vehicles at medium voltage (2.4-13.8 kV) make voltage drop the dominant design constraint.

Step-up transformers at the surface compensate for cable drop, with VD calculations performed at the full locked-rotor current to ensure the motor starts at depth.

Real-World Usage Scenarios

Remote pump station feeder that kept tripping

A water utility installed a 75 HP submersible well pump 1,200 ft from the MCC. The consulting engineer sized the feeder for ampacity: 96 A FLA → #2 AWG copper (115 A at 75°C). The pump started reliably during commissioning but tripped on undervoltage during summer peak demand when the utility voltage sagged to 450V. Investigation revealed the starting voltage drop at 6 × 96 = 576 A LRA was: VD = (1.732 × 1,200 × 12.9 × 576) ÷ 66,360 = 232 V — meaning motor terminal voltage was 460 − 232 = 228 V, only 49.6% of rated and far below the 85% minimum. Even at running FLA, VD = (1.732 × 1,200 × 12.9 × 96) ÷ 66,360 = 38.8 V (8.4%), exceeding the 5% feeder limit. The fix: replaced with 350 kcmil copper (350,000 CM), reducing starting VD to (1.732 × 1,200 × 12.9 × 576) ÷ 350,000 = 44.1 V (9.6%), which combined with the 450V utility supply gave 405.9V at the motor (88.2% — above the 85% threshold for pump start). Running VD dropped to 7.3V (1.6%), fully compliant.

LED parking lot lights dim at the far end of the row

A retail center retrofit installed 480V LED pole lights on a single 20 A circuit, 8 fixtures at 2.5 A each, spaced 80 ft apart along a 640 ft run. The contractor used #12 AWG copper (ampacity adequate for 20 A) and terminated daisy-chain style. The first three poles were bright; poles 6-8 were visibly dim. The problem: the full 20 A flows through the first 80 ft segment, then 17.5 A through the next 80 ft, and so on — each segment has a different voltage drop. The total accumulated voltage drop calculation treating the load as concentrated at the midpoint (320 ft) approximates: VD = (2 × 320 × 12.9 × 20) ÷ 6,530 = 25.3 V = 5.27% — exceeding the 3% branch limit. A precise step-by-step calculation showed pole 8 received only 449V (6.5% drop). The LED drivers, rated for 347-480V ±10%, were near the lower limit and reduced output. The solution: re-pull with #8 AWG (16,510 CM) reducing VD to (2 × 320 × 12.9 × 20) ÷ 16,510 = 10.0 V (2.08%) with uniform brightness across all eight poles.

Hospital operating room voltage exceeded IEEE 519 limits

A new hospital wing's operating rooms required isolated power systems per NEC 517.160, with maximum 2.0V line-to-ground leakage and stringent voltage stability for surgical lasers and imaging equipment. The 208/120V panelboard was located 180 ft from the main switchboard, feeding 60 A of mixed OR loads. The design engineer initially specified #4 AWG copper (41,740 CM) giving VD = (1.732 × 180 × 12.9 × 60) ÷ 41,740 = 5.78 V (2.78%) — acceptable for normal NEC purposes. However, the surgical laser manufacturer's specification required voltage regulation within ±3% at the receptacle, and the 2.78% in the feeder alone consumed nearly the entire budget before the branch circuit drop. Combined with the branch circuit VD (an additional 60 ft of #10 AWG at 20 A: VD = (2 × 60 × 12.9 × 20) ÷ 10,380 = 2.98 V = 2.49%), the total drop was 8.76V (4.21%) — outside the laser's tolerance. The engineering resolution: upgrade the feeder to #1 AWG (83,690 CM) for a feeder VD of (1.732 × 180 × 12.9 × 60) ÷ 83,690 = 2.88V (1.38%), keeping the combined VD at 2.88 + 2.98 = 5.86V (2.82%), within specification and ensuring the $350,000 laser system would operate reliably without nuisance shutdowns during procedures.

Common Mistakes to Avoid

1

Using the wrong length (one-way vs. round-trip)

The formula already includes the 2× or 1.732× multiplier for return path, so you must enter the ONE-WAY cable length — not the round-trip distance. A designer who enters the round-trip length of 300 ft (instead of the 150 ft one-way distance) will calculate double the actual voltage drop — VD overestimated by 100%. This leads to unnecessary conductor upsizing: a circuit that would be fine with #2 AWG gets spec'd as #2/0 AWG, adding thousands in material cost and requiring larger conduit. Conversely, entering one-way length when the formula is manually rearranged without the 2× factor leads to underestimating VD by 50%, which can cause equipment underperformance that is only discovered during commissioning.

2

Neglecting to check AC reactance for large conductors

The K-factor voltage drop formula uses DC resistance only. For conductors #2 AWG and larger, AC impedance (resistance + inductive reactance) becomes significant, particularly in steel conduit where the magnetic field couples to the raceway. At #4/0 AWG in steel conduit, the AC impedance can be 15-20% higher than the DC resistance alone, meaning actual voltage drop exceeds the simple calculation. The IEEE 141 Red Book provides exact AC impedance tables per conductor size and conduit type. A 400 A feeder using 500 kcmil copper in steel conduit over 500 ft: DC VD = (1.732 × 500 × 12.9 × 400) ÷ 500,000 = 8.94 V. But AC effective impedance (Z_eff = 0.029 Ω/1000 ft from IEEE 141 Table) gives VD = 400 × 0.029 × (500/1000) × 1.732 = 10.05 V — 12.4% higher than the DC calculation. For precision engineering on circuits above 200 A, use IEEE 141 AC impedance data rather than the simplified K-factor method.

3

Assuming balanced loading eliminates voltage drop in the neutral

In a perfectly balanced three-phase circuit, neutral current IS zero and there IS no neutral voltage drop. But real-world circuits are never perfectly balanced, especially 208/120V systems where single-phase loads are distributed across phases. A panel with A-phase at 45 A, B-phase at 38 A, and C-phase at 52 A produces a neutral current of approximately 12 A (vector sum). This neutral current causes a voltage drop in the neutral conductor that shifts the phase-to-neutral voltages — overvoltage on lightly loaded phases, undervoltage on heavily loaded phases. If the neutral conductor is sized per NEC 220.61 (which often permits a reduced neutral), the neutral voltage drop may be significant. A common error: running a voltage drop calculation assuming 0 A neutral and a full-size neutral, while the actual installation has a 70% reduced neutral and significant imbalance. For critical circuits with substantial single-phase loading, calculate VD using actual neutral current and verify neutral-to-ground voltage at the furthest outlet does not exceed 2-3V.

Industry Standards Referenced

NEC Article 210 NEC Article 215 NEC Article 695 IEEE 141 ASHRAE 90.1

Frequently Asked Questions

What is the maximum allowable voltage drop per NEC?

NEC 210.19 Informational Note No. 4 recommends: branch circuits — maximum 3% voltage drop at the farthest outlet. Feeders — maximum 2%. Combined feeder + branch — maximum 5%. These are Informational Notes, meaning they are guidance, not enforceable code requirements (enforceable requirements use the word 'shall'). However, they are universally followed in design practice and often written into project specifications, making them contractually binding. Energy codes such as ASHRAE 90.1-2019 §8.4.1 do make feeder voltage drop limits enforceable (maximum 2% for feeders) as part of mandatory energy efficiency provisions. Fire pump circuits under NEC 695.7 carry a mandatory and specific 15% maximum during motor starting (locked-rotor current) and 5% at running load — these are enforceable 'shall' requirements. Additionally, IEC 60364-5-52 for international projects specifies 3% for lighting and 5% for other uses from the origin of the installation.

How do I reduce voltage drop on a long cable run?

Four options, in order of typical cost-effectiveness: (1) Increase conductor size — the most common solution. Going from #12 to #10 AWG increases cross-sectional area by 59% (6,530 to 10,380 CM) and reduces VD proportionally. (2) Increase system voltage — doubling the voltage halves the current for the same power, reducing VD by 50%. For a 10 kW motor, 208V requires 27.8 A vs. 480V requiring 12.0 A — same kW, half the VD. (3) Reduce distance — relocate the panel or transformer closer to the load. For outdoor or campus installations, adding a pad-mounted transformer near the load building can reduce feeder length from thousands of feet to hundreds. (4) Parallel conductors — running two identical cables per phase halves the current per conductor, reducing VD by 50%. NEC 310.10(H) requires paralleled conductors to be the same length, material, cross-sectional area, insulation type, and terminated in the same manner. For existing installations where recabling is impractical, options include: installing a boost transformer at the load end, adjusting transformer primary taps, or using power conditioning equipment (e.g., constant-voltage transformers for sensitive single-phase loads).

What's the difference between copper and aluminum for voltage drop?

Copper resistivity (K=12.9) is about 39% lower than aluminum (K=21.2). This means an aluminum conductor needs approximately 64% more cross-sectional area (21.2 ÷ 12.9 = 1.64) to achieve the same voltage drop as a copper conductor. For equal ampacity per NEC 310.16, aluminum conductors are typically 1-2 AWG sizes larger than copper — but aluminum is roughly 50% lighter and 30-50% cheaper per ampere-foot, dominating utility transmission and distribution, large service entrance cables (residential 4/0 Al for 200 A services), and commercial feeders above 400 A. In commercial building branch circuits (15-60 A), copper is overwhelmingly preferred due to smaller conduit fill, better termination reliability (aluminum oxide is an insulator that must be wire-brushed and coated with anti-oxidant compound), and avoidance of the thermal expansion mismatch that can loosen aluminum terminations over repeated load cycling. For large commercial feeders (400-4000 A), the cost advantage of aluminum often makes it the default choice, with careful attention to AL/CU-rated lugs and proper torque procedures per manufacturer instructions.

How does power factor affect voltage drop calculations?

The simple K-factor formula (DC resistance method) assumes unity power factor and gives acceptable results for conductors #2 AWG and smaller where inductive reactance is negligible. For larger conductors, power factor significantly affects voltage drop. The exact AC formula is: VD = I × (R × cos φ + X × sin φ) × L × √n, where R is AC resistance (Ω/ft), X is inductive reactance (Ω/ft), and φ is the power factor angle. At lagging power factor (inductive loads: motors, transformers), the voltage drop is HIGHER than the unity-PF calculation because the inductive reactance component adds to the drop — a 0.85 PF motor circuit experiences roughly 10-15% more VD than the simple DC calculation predicts. At leading power factor (capacitive loads, lightly loaded long cables with capacitance), voltage RISE can occur (Ferranti effect). For a 500 A, 480V feeder with 0.80 PF at 750 ft using 750 kcmil copper: DC method → VD = (1.732 × 750 × 12.9 × 500) ÷ 750,000 = 11.2 V (2.33%). AC exact (R=0.0172, X=0.0340 Ω/1000 ft): VD = 1.732 × 500 × [(0.0172 × 0.80) + (0.0340 × 0.60)] × (750/1000) = 22.2 V (4.63%) — nearly double the DC estimate. For precision work on conductors #2/0 and larger, consult IEEE 141 AC impedance tables with actual load power factor.

Why does NEC Chapter 9 Table 8 list DC resistance at 75°C?

NEC Table 8 conductor properties are listed at 75°C because this is the assumed operating temperature for most building wire types under full ampacity loading. Copper's resistance increases with temperature: R_T = R_25°C × [1 + 0.00393 × (T − 25)]. At 75°C, resistance is approximately 19.7% higher than at 25°C. Using the 75°C value is conservative for steady-state voltage drop because the conductor will be at or near 75°C when carrying full rated current. For cold-start conditions (e.g., checking voltage for motor starting when the conductor is at ambient temperature), the actual VD may be slightly lower than calculated. Conversely, for rooftop conduits in direct sun where ambient plus solar gain can reach 60-70°C, the conductor temperature may exceed 75°C and resistance increases further — NEC Table 310.15(B)(1) provides temperature correction factors that can be applied to the resistance values for installations above 30°C ambient.

How do I calculate voltage drop for a mixed single-phase/three-phase installation?

For a feeder serving both three-phase and single-phase loads, calculate VD separately for each portion. The three-phase portion uses VD_3Φ = (1.732 × L × K × I_3Φ) ÷ CM. The single-phase portions are served line-to-neutral and use VD_1Φ = (2 × L_1Φ × K × I_1Φ) ÷ CM for each phase conductor + neutral. The worst-case phase voltage (line-to-neutral) is the critical value. If the single-phase loads are reasonably balanced across all three phases, use the phase with the highest current for the VD check. For a mixed panel (100 A 3Φ motor + 40 A miscellaneous 1Φ on each phase), the design approach is: (a) calculate feeder VD using 3Φ formula at the total phase current (100 + 40 = 140 A per phase), (b) for each 1Φ branch circuit, calculate its VD from the panel to the load using the 1Φ formula, (c) sum the feeder VD% + worst branch VD% to verify the 5% combined limit.

Reviewed for accuracy

Cross-referenced against NEC Chapter 9 Table 8 conductor properties and IEEE 141 voltage drop methodology · Last reviewed: July 26, 2026

All calculations are for reference only. Always verify with manufacturer data and a qualified engineer for critical applications. Learn about our editorial process.

Related Conversions

See all Electrical Design converters